Приказ основних података о дисертацији

Тransverse differential protection of double circuit overhead lines

dc.contributor.advisorStojanović, Zoran
dc.contributor.otherŠekara, Tomislav
dc.contributor.otherJanda, Žarko
dc.contributor.otherĐurišić, Željko
dc.contributor.otherKrstivojević, Jelisaveta
dc.creatorForcan, Miodrag
dc.date.accessioned2020-07-15T10:23:36Z
dc.date.available2020-07-15T10:23:36Z
dc.date.issued2020-03-09
dc.identifier.urihttp://eteze.bg.ac.rs/application/showtheses?thesesId=7463
dc.identifier.urihttps://fedorabg.bg.ac.rs/fedora/get/o:22296/bdef:Content/download
dc.identifier.urihttp://vbs.rs/scripts/cobiss?command=DISPLAY&base=70036&RID=17087753
dc.identifier.urihttps://nardus.mpn.gov.rs/handle/123456789/17179
dc.description.abstractDvostruki nadzemni vodovi (DNV) se često projektuju i grade u elektroenergetskim sistemima (EES) sa osnovnim ciljem povećanja kapaciteta i pouzdanosti prenosa električne energije. Najčešće povezuju dva aktivna visokonaponska dijela EES-a, ali se mogu pronaći i u radijalno napajanim mrežama industrijskih nivoa napona, za šta je karakterističan primjer napajanje udaljenih industrijskih zona i rudnika u razvijenim državama. Zbog postojanja dva paralelna sistema vodova na zajedničkim stubovima duž iste trase, aktivne su elektromagnetske sprege šest provodnika, što značajno komplikuje realizaciju osjetljive i selektivne relejne zaštite u odnosu na standardne slučajeve relejne zaštite jednostrukih nadzemnih vodova. Od relejne zaštite DNV-a očekuje se selektivnost u pogledu razlikovanja kvarova unutar i izvan štićene dionice, lociranja na kom od dva paralelna voda se nalazi kvar i određivanja faza koje su obuhvaćene petljom kvara. U okviru ove doktorske disertacije analizirani su postojeći i razvijeni novi algoritmi u cilju poboljšanja osjetljivosti i obezbjeđivanja selektivnosti usmjerene poprečne diferencijalne zaštite DNV-a. Kao preduslov za kvalitetan istraživački proces, na početku je definisan precizan matematički model DNV-a, praćen odgovarajućom softverskom implementacijom i detaljnom metodologijom proračuna podužnih električnih parametara. Potom je data i komparativna analiza uticaja različitih transpozicija provodnika DNV-a na signale struja u asimetričnim režimima rada. Nakon formiranja i implementacije modela DNV-a, razvijen je interaktivni simulator rada relejne zaštite primjenom softverskog paketa MATLAB, u svrhu detaljnog simulacionog ispitivanja postojećih i novorazvijenih algoritama. U prvom koraku istraživačkog procesa analizirani su i detaljno ispitivani tradicionalni koncepti relejne zaštite DNV-a. Putem odgovarajuće komparativne analize utvrđene su prednosti i mane koncepta poprečne diferencijalne zaštite u odnosu na koncept distantne zaštite. Drugi korak istraživačkog procesa je posvećen analizi i ispitivanju posebne klase algoritama poprečne diferencijalne zaštite koji u svom radu ne koriste naponske signale. Za slučaj dvostrano napajanog DNV-a, vršeno je ispitivanje i data je komparativna analiza rezultata rada dva najpoznatija algoritma poprečne diferencijalne zaštite, zasnovana na priraštajima strujnih signala. U trećem koraku istraživanja predložen je novi algoritam zasnovan na promjeni faznih uglova strujnih signala za usmjerenu poprečnu diferencijalnu zaštitu radijalnog DNV-a. Osnovni cilj razvoja novog algoritma je zasnovan na pretpostavci da je moguće poboljšati osjetljivost usmjerene poprečne diferencijalne zaštite za slučaj radijalnog DNV-a, u odnosu na postojeće algoritme koji u svom radu koriste samo signale struja. Zatim je za slučaj radijalnog DNV-a vršeno novo ispitivanje i data je komparativna analiza rezultata rada postojećeg poznatog algoritma zasnovanog na priraštajima strujnih signala i predloženog novog algoritma zasnovanog na promjeni faznih uglova strujnih signala.sr
dc.description.abstractDouble circuit lines (DCL) are often designed and used in the power systems with the main goal of improving the capacity and reliability of the power transmission. They usually connect two high-voltage active networks, but also can be found in industry-level voltage radial networks in developed countries with typical application of supplying power to remote industrial areas and mines. Due to the existence of two parallel lines on the same transmission towers, along the same route, electromagnetic couplings of six conductors significantly complicate realization of the sensitive and selective relay protection systems when compared to relay protection systems for typical transmission lines consisting of three conductors. Relay protection of DCL is expected to be selective in the distinction of the faults inside and outside of the protection zone, as well as in the distinction of the faulted and healthy line, and it is additionally required for protection to detect which phases are faulted. Within this thesis, the existing and new algorithms are developed in order to improve sensitivity and ensure selectivity of the transverse differential protection of DCL. A precise mathematical model of DCL is initially defined as a precondition for quality research process, which is followed by the corresponding software implementation and detailed methodology of longitudinal electrical parameters calculation. Then the comparative analysis of the impact of different transpositions of DCL conductors on current signals in unbalanced operation mode is presented. After defining and implementing DCL model, an interactive simulator of relay protection is developed using a software package MATLAB with the main goal of enabling detailed simulation analysis of the existing and newly created algorithms. Traditional concepts of DCL relay protection operation are analysed and tested in the first step of the research process. The advantages and drawbacks of transverse differential protection concept are determined and compared with those corresponding to distance protection concept. The second step of the research process includes the analysis and testing of the special algorithms for transverse differential protection that do not require the voltage signals for operation. For the case of doubly-fed DCL, two selected algorithms based on increments of current signals are tested and the comparative analysis of the obtained results is given. In the third step of the research process a new algorithm, based on the changes of phase angles of current signals, is proposed for protection of radial DCL. The main goal behind the development of the new algorithm is based on the assumption that is possible to additionally improve sensitivity of directional transverse differential protection in the case of radial DCL, when compared to existing algorithms using only current signals for operation. Then the new testing is performed in the case of radial DCL in order to compare the existing well-known algorithm based on increments of current signals with newly proposed algorithm based on the changes of phase angles of current signals.en
dc.formatapplication/pdf
dc.languagesr
dc.publisherУниверзитет у Београду, Електротехнички факултетsr
dc.rightsopenAccessen
dc.rights.urihttps://creativecommons.org/licenses/by-nc-nd/4.0/
dc.sourceУниверзитет у Београдуsr
dc.subjectdvostruki nadzemni vodsr
dc.subjectdouble circuit linesen
dc.subjecttransverse differential protectionen
dc.subjectdigital relay protection algorithmsen
dc.subjectsingle-pole reclosingen
dc.subjectpoprečna diferencijalna zaštitasr
dc.subjectalgoritmi za digitalne relejne zaštitesr
dc.subjectjednofazno automatsko ponovno uključenjesr
dc.titlePoprečna diferencijalna zaštita dvostrukih nadzemnih vodovasr
dc.title.alternativeТransverse differential protection of double circuit overhead linesen
dc.typedoctoralThesisen
dc.rights.licenseBY-NC-ND
dc.identifier.fulltexthttps://nardus.mpn.gov.rs/bitstream/id/63956/Disertacija.pdf
dc.identifier.fulltexthttps://nardus.mpn.gov.rs/bitstream/id/63957/IzvestajKomisije22796.pdf
dc.identifier.rcubhttps://hdl.handle.net/21.15107/rcub_nardus_17179


Документи за докторску дисертацију

Thumbnail
Thumbnail

Ова дисертација се појављује у следећим колекцијама

Приказ основних података о дисертацији